dc-voltage |
12
|
rated-current |
6.3
|
current-range |
0 ~ 6.3A
|
input-voltage-range |
85 ~ 264VAC 120 ~ 370VDC
|
rated-power |
76
|
working-temp |
'-10 ~ +60℃ (Refer to "Derating Curve")
|
storage-temp-humidity |
'-20 ~ +85℃, 10 ~ 95% RH
|
ripple-noise |
100mVp-p
|
voltage-adj-range |
12 ~ 14V
|
voltage-tolerance |
±2.0%
|
emc-emission |
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3
|
line-regulation |
±0.5%
|
load-regulation |
±1.0%
|
hold-up-time |
60ms/230VAC 12ms/115VAC at full load
|
over-temperature |
85℃±5℃ (TSW1) detect on heat sink of power transistor Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
working-humidity |
20 ~ 90% RH non-condensing
|
efficiency |
76%
|
frequency-range |
47 ~ 63Hz
|
ac-current |
1.6A/115V 0.96A/230V
|
inrush-current |
COLD START 20A/115VAC 40A/230VAC
|
isolation-resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
|
safety-standards |
UL508, TUV EN60950-1 approved
|
leakage-current |
1mA in 240VAC
|
overload |
105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
|
over-voltage |
Protection type : Shut down o/p voltage, re-power on to recover 15 ~ 16.5V
|
temp-coefficient |
±0.03%/℃ (0 ~ 50℃)
|
set-up-rise-time |
1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full load
|
with-stand-voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
emc-immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
|
mtbf |
123.1K hrs min. MIL-HDBK-217F (25℃)
|
dimension |
55.5*125.2*100mm (W*H*D)
|
packing |
0.6Kg; 20pcs/13Kg/1.29CUFT
|