DC VOLTAGE |
24
|
RATED CURRENT |
3.2
|
CURRENT RANGE |
0 ~ 3.2A
|
INPUT VOLTAGE RANGE |
85 ~ 264VAC 120 ~ 370VDC
|
RATED POWER |
76.8
|
WORKING TEMP |
-10 ~ +60℃ (Refer to "Derating Curve")
|
STORAGE TEMP HUMIDITY |
-20 ~ +85℃, 10 ~ 95% RH
|
RIPPLE & NOISE |
150mVp-p
|
VOLTAGE ADJ.RANGE |
24 ~ 28V
|
VOLTAGE TOLERANCE |
±1.0%
|
EMC EMISSION |
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3
|
LINE REGULATION |
±0.5%
|
LOAD REGULATION |
±1.0%
|
HOLD UP TIME |
60ms/230VAC 12ms/115VAC at full load
|
OVER TEMPERATURE |
85℃±5℃ (TSW1) detect on heat sink of power transistor Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
WORKING HUMIDITY |
20 ~ 90% RH non-condensing
|
EFFICIENCY |
80%
|
FREQUENCY RANGE |
47 ~ 63Hz
|
AC CURRENT |
1.6A/115V 0.96A/230V
|
INRUSH CURRENT |
COLD START 20A/115VAC 40A/230VAC
|
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
|
SAFETY STANDARDS |
UL508, TUV EN60950-1 approved
|
LEAKAGE CURRENT |
1mA in 240VAC
|
OVERLOAD |
105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
|
OVER VOLTAGE |
Protection type : Shut down o/p voltage, re-power on to recover 29 ~ 34V
|
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃)
|
SET UP, RISE TIME |
1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full load
|
WITH STAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
|
MTBF |
123.1K hrs min. MIL-HDBK-217F (25℃)
|
DIMENSION |
55.5*125.2*100mm (W*H*D)
|
PACKING |
0.6Kg; 20pcs/13Kg/1.29CUFT
|