| dc-voltage |
24
|
| rated-current |
3.2
|
| current-range |
0 ~ 3.2A
|
| input-voltage-range |
85 ~ 264VAC 120 ~ 370VDC
|
| rated-power |
76.8
|
| working-temp |
'-10 ~ +60℃ (Refer to "Derating Curve")
|
| storage-temp-humidity |
'-20 ~ +85℃, 10 ~ 95% RH
|
| ripple-noise |
150mVp-p
|
| voltage-adj-range |
24 ~ 28V
|
| voltage-tolerance |
±1.0%
|
| emc-emission |
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3
|
| line-regulation |
±0.5%
|
| load-regulation |
±1.0%
|
| hold-up-time |
60ms/230VAC 12ms/115VAC at full load
|
| over-temperature |
85℃±5℃ (TSW1) detect on heat sink of power transistor Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
| working-humidity |
20 ~ 90% RH non-condensing
|
| efficiency |
80%
|
| frequency-range |
47 ~ 63Hz
|
| ac-current |
1.6A/115V 0.96A/230V
|
| inrush-current |
COLD START 20A/115VAC 40A/230VAC
|
| isolation-resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
|
| safety-standards |
UL508, TUV EN60950-1 approved
|
| leakage-current |
1mA in 240VAC
|
| overload |
105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
| vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
|
| over-voltage |
Protection type : Shut down o/p voltage, re-power on to recover 29 ~ 34V
|
| temp-coefficient |
±0.03%/℃ (0 ~ 50℃)
|
| set-up-rise-time |
1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full load
|
| with-stand-voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
| emc-immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
|
| mtbf |
123.1K hrs min. MIL-HDBK-217F (25℃)
|
| dimension |
55.5*125.2*100mm (W*H*D)
|
| packing |
0.6Kg; 20pcs/13Kg/1.29CUFT
|