DC VOLTAGE |
15
|
RATED CURRENT |
1
|
CURRENT RANGE |
0 ~1A
|
INPUT VOLTAGE RANGE |
85 ~ 264VAC 120 ~ 370VDC
|
RATED POWER |
15
|
WORKING TEMP |
-20 ~ +60℃ (Refer to "Derating Curve")
|
STORAGE TEMP HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH
|
RIPPLE & NOISE |
120mVp-p
|
VOLTAGE ADJ.RANGE |
13.5 ~ 16.5V
|
VOLTAGE TOLERANCE |
±1.0%
|
EMC EMISSION |
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
|
LINE REGULATION |
±1.0%
|
LOAD REGULATION |
±1.0%
|
HOLD UP TIME |
70ms/230VAC 16ms/115VAC at full load
|
WORKING HUMIDITY |
20 ~ 90% RH non-condensing
|
EFFICIENCY |
83.5%
|
FREQUENCY RANGE |
47 ~ 63Hz
|
AC CURRENT |
0.88A/115VAC 0.48A/230VAC
|
INRUSH CURRENT |
COLD START 35A/115VAC 65A/230VAC
|
ISOLATION RESISTANCE |
I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
|
SAFETY STANDARDS |
UL60950-1, TUV EN60950-1 approved, design refer to EN50178
|
OVERLOAD |
105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is remov
|
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
|
OVER VOLTAGE |
Protection type : Shut off o/p voltage, clamping by zener diode 17.25 ~ 20.25V
|
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃)
|
SET UP, RISE TIME |
1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full load
|
WITH STAND VOLTAGE |
I/P-O/P:3KVAC
|
EMC IMMUNITY |
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
|
MTBF |
1172.3K hrs min. MIL-HDBK-217F (25℃)
|
DIMENSION |
25*93*56mm (W*H*D)
|
PACKING |
0.1Kg; 140pcs/15Kg/0.92CUFT
|