dc-voltage |
27.6
|
rated-current |
1.4
|
current-range |
0 ~ 1.4A
|
PEAK 5S |
1.7A
|
rated-power |
38.6
|
ripple-noise |
200mVp-p
|
voltage-adj-range |
'+15,-5%
|
voltage-tolerance |
±1.0%
|
line-regulation |
±1.0%
|
load-regulation |
±1.0%
|
set-up-rise-time |
500ms, 30ms/230VAC 1200ms, 30ms/115VAC at full load
|
hold-up-time |
50ms/230VAC 16ms/115VAC at full load
|
input-voltage-range |
85 ~ 264VAC 120 ~ 370VDC
|
frequency-range |
47 ~ 63Hz
|
efficiency |
86%
|
ac-current |
0.75A/115VAC 0.5 A/230VAC
|
inrush-current |
COLD START 45A
|
LEAKAGE CURRENT |
<2mA / 240VAC
|
temp-compensation |
By NTC (not provide with the power supply)
|
output-voltage-sensor |
L=output voltage +0.2 ~ 0.7V(AC OK); L=0V(AC Fail)
|
overload |
Protection type : Hiccup mode, recovers automatically after fault condition is removed 1.7 ~ 2.3A rated output power
|
over-voltage |
Protection type : Shut down o/p voltage, re-power on to recover 33.1 ~ 38.5V
|
working-temp |
'-20 ~ +60℃(Refer to output load derating curve)
|
working-humidity |
20 ~ 90% RH non-condensing
|
storage-temp-humidity |
'-40 ~ +85℃, 10 ~ 95% RH
|
temp-coefficient |
±0.05%/℃(0 ~ 45℃)
|
vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
|
safety-standards |
UL60950-1, CB(IEC60950-1),CCC GB4943 approved
|
with-stand-voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
isolation-resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
|
emc-emission |
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,3
|
emc-immunity |
Compliance to EN61000-4-2, 3, 4, 5, 6, 8,11, ENV50204, EN55024, EN61000-6-1, light industry level, criteria A
|
mtbf |
523.3Khrs min. MIL-HDBK-217F (25℃)
|
dimension |
99*97*36mm (L*W*H)
|
packing |
0.37Kg; 45pcs/17.7Kg/1CUFT
|
نقد و بررسیها