| dc-voltage | 24 |
|---|---|
| rated-current | 10 |
| current-range | 0 ~ 10A |
| rated-power | 240 |
| ripple-noise | 80mVp-p |
| voltage-adj-range | 24 ~ 28V |
| voltage-tolerance | ±1.0% |
| line-regulation | ±0.5% |
| load-regulation | ±0.5% |
| set-up-rise-time | 1200ms, 40ms, 20ms/400VAC 800ms, 40ms, 40ms/500VAC at full load |
| input-voltage-range | Three-Phase 340 ~ 550VAC (Dual phase operation possible) 480 ~ 780VDC |
| frequency-range | 47 ~ 63Hz |
| efficiency | 89% |
| ac-current | 0.95A/400VAC 0.75A/500VAC |
| inrush-current | COLD START 50A |
| LEAKAGE CURRENT | <3.5mA / 530VAC |
| overload | 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed |
| over-voltage | Protection type : Shut down o/p voltage, re-power on to recover 30 ~ 36V |
| over-temperature | 100℃±5℃ (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
| working-temp | '-20 ~ +70℃ (Refer to "Derating Curve") |
| working-humidity | 20 ~ 90% RH non-condensing |
| storage-temp-humidity | '-40 ~ +85℃, 10 ~ 95% RH |
| temp-coefficient | ±0.03%/℃ (0 ~ 50℃) |
| vibration | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
| safety-standards | UL508, UL60950-1, TUV EN60950-1 approved |
| with-stand-voltage | I/P-O/P:3KVAC , I/P-FG:1.5KVAC , O/P-FG:0.5KVAC |
| isolation-resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
| emc-emission | Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B |
| emc-immunity | Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A |
| mtbf | 114.6K hrs min. MIL-HDBK-217 (25℃) |
| dimension | 125.5*125.2*100mm (W*H*D) |
| packing | 1.3Kg; 12pcs/16.6Kg/1.29CUFT |