| dc-voltage | 
			12 
 | 
		
			
			| rated-current | 
			6.3 
 | 
		
			
			| current-range | 
			0 ~ 6.3A 
 | 
		
			
			| input-voltage-range | 
			85 ~ 264VAC 120 ~ 370VDC 
 | 
		
			
			| rated-power | 
			76 
 | 
		
			
			| working-temp | 
			'-10 ~ +60℃ (Refer to "Derating Curve") 
 | 
		
			
			| storage-temp-humidity | 
			'-20 ~ +85℃, 10 ~ 95% RH 
 | 
		
			
			| ripple-noise | 
			100mVp-p 
 | 
		
			
			| voltage-adj-range | 
			12 ~ 14V 
 | 
		
			
			| voltage-tolerance | 
			±2.0% 
 | 
		
			
			| emc-emission | 
			Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3 
 | 
		
			
			| line-regulation | 
			±0.5% 
 | 
		
			
			| load-regulation | 
			±1.0% 
 | 
		
			
			| hold-up-time | 
			60ms/230VAC 12ms/115VAC at full load 
 | 
		
			
			| over-temperature | 
			85℃±5℃ (TSW1) detect on heat sink of power transistor Protection type : Shut down o/p voltage, recovers automatically after temperature goes down 
 | 
		
			
			| working-humidity | 
			20 ~ 90% RH non-condensing 
 | 
		
			
			| efficiency | 
			76% 
 | 
		
			
			| frequency-range | 
			47 ~ 63Hz 
 | 
		
			
			| ac-current | 
			1.6A/115V 0.96A/230V 
 | 
		
			
			| inrush-current | 
			COLD START 20A/115VAC 40A/230VAC 
 | 
		
			
			| isolation-resistance | 
			I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH 
 | 
		
			
			| safety-standards | 
			UL508, TUV EN60950-1 approved 
 | 
		
			
			| leakage-current | 
			1mA in 240VAC 
 | 
		
			
			| overload | 
			105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 
 | 
		
			
			| vibration | 
			10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 
 | 
		
			
			| over-voltage | 
			Protection type : Shut down o/p voltage, re-power on to recover 15 ~ 16.5V 
 | 
		
			
			| temp-coefficient | 
			±0.03%/℃ (0 ~ 50℃) 
 | 
		
			
			| set-up-rise-time | 
			1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full load 
 | 
		
			
			| with-stand-voltage | 
			I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC 
 | 
		
			
			| emc-immunity | 
			Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A 
 | 
		
			
			| mtbf | 
			123.1K hrs min. MIL-HDBK-217F (25℃) 
 | 
		
			
			| dimension | 
			55.5*125.2*100mm (W*H*D) 
 | 
		
			
			| packing | 
			0.6Kg; 20pcs/13Kg/1.29CUFT 
 | 
		
	
			